- Limit Switches[7]
- Contactors[7]
- Circuit Breakers[7]
- Other Hand Tools[7]
- Relays[7]
- Counters[2]
- Voltage Meters[3]
- Inverters & Converters[1]
- Terminals[1]
- Other Passive Components[6]
- Contact Person : Ms. Wan Lisa
- Company Name : Shanghai Shinuo Electric Co., Ltd.
- Tel : 0086-577-61728001
- Fax : 0086-577-61728006
- Address : Zhejiang,Yueqing,Chandong industrial zone
- Country/Region : China
- Zip : 00000
Thermal overload protection relay JR20-160L VR20-160L
1.Specification
LR20(VR20) series thermal overload relay are suitable for overload and phase-failure protection of AC motors with frequency of 50/60Hz, voltage up to 660v, current up to 0.16-630A under 8-hours duty or uninterrupted duty.Functions provided by these relays are: phase-failure protection, temperature compensation, ON/OFF indication, and manual/automatic reset.
Applicable Standards: National Standard: GB 14048, International Standards: IEC 60947-4-1 LR20- L, L shows installed as single units.The relays can be mounted onto contactors or installed as single units.2.Operation condition
(1)The altitude couldn t exceed 2000m.(2)Ambient temperature: -5 ~+55 and the average temperature no more than +35 in 24hours.(3)Atmosphere: Comparative humidity no more than 50% at max +40 , and it may be higher at a lower temperature. The lowest average temperature no more than +20 in the wettest month.(4)The maximum average comparative humidity of this month couldn t exceed 90%, The change of temperature leading to dew on the product must be considered.(5)Class of pollution: Class 3.(6)The slope between installation surface and vertical surface couldn t exceed 5o.(7)Keeping away from explosive, corrosive and electric atomy.(8)Keeping dry.(9)The product should be used and installed at certain place without any shock, vibration etc.
3.Features
Three-phase thermal relays with release class 10A.With differential phase-failure protection.With continuous current adjusting scale.With temperature compensation.With ON/OFF indicator.With TEST (OFF) buttonWith Manual/Auto reset button.
With Auxiliary contacts 1 NO+1 NC insulated each other.Mounting: install as a single unit.
4. Main Technical
Type | Number | 5WSetting Range(A) | For Contactor |
JR20-10L | 1R | 0.1~0.15 | CJ20 -10 |
2R | 0.15~0.23 | ||
3R | 0.23~0.35 | ||
4R | 0.35~0.53 | ||
5R | 0.53~0.8 | ||
6R | 0.8~1.2 | ||
7R | 1.2~1.8 | ||
8R | 1.8~2.6 | ||
9R | 2.6~3.8 | ||
10R | 3.2~4.8 | ||
11R | 4~6 | ||
12R | 5~7 | ||
13R | 6~8.4 | ||
14R | 7~10 | ||
15R | 8.6~11.6 | ||
JR20-16L | 1S | 3.6~5.4 | CJ20 -10 -16 |
2S | 5.4~8 | ||
3S | 8~12 | ||
4S | 10~14 | ||
5S | 12~16 | ||
6S | 14~18 | ||
JR20-25L | 1T | 7.8~11.6 | CJ20 -16 -25 |
2T | 11.6~17 | ||
3T | 17~25 | ||
4T | 21~29 | ||
JR20-63L | 1U | 16~24 | CJ20 -40 -63 |
2U | 24~36 | ||
3U | 32~47 | ||
4U | 40~55 | ||
5U | 47~62 | ||
6U | 55~71 | ||
JR20-160L | 1W | 33~47 | CJ20 -100 -160 |
2W | 47~63 | ||
3W | 63~84 | ||
4W | 74~98 | ||
5W | 85~115 | ||
6W | 100~130 | ||
7W | 115~150 | ||
8W | 130~170 | ||
9W | 144~176 | ||
JR20-250L | 1X | 130~195 | CJ20 -250 |
2X | 167~250 | ||
JR20-400L | 1Y | 200~300 | CJ20 -400 |
2Y | 267~400 | ||
JR20-630L | 1Z | 320~480 | CJ20 -630 |
2Z | 420~630 |
MOTION CHARACTERISTIC:THREE-PHASE BALANCE MOTION TIME
No | Times the setting current | Motion time | Start conidition | Ambient temperature | ||
1 | 1.05 | >2h | cold state | 20±5ºC | ||
2 | 1.2 | <2h | heat state (Following the No.1 test) | |||
3 | 1.5 | <4min | ||||
4 | 7.2 | 10A | 2s < Tp ≤ 10s | ≤ 63A | cold state | |
10 | 4s < Tp ≤10s | >63A |
PHASE-LOSING MOTION CHARACTERISTIC
No | Times the setting current | Motion time | Start condition | Ambient temperature | |
Any two phase | Another phase | ||||
1 | 1.0 | 0.9 | >2h | cold state | 20±5ºC |
2 | 1.15 | 0 | <2h | heat state (Following the No.1 test) |
5.Overall and Mounting Dimmensions
6.The time-current curves characteristic
7.Product photo
Thermal overload protection relay JR20-160L VR20-160L