- Limit Switches[7]
- Contactors[7]
- Circuit Breakers[7]
- Other Hand Tools[7]
- Relays[7]
- Counters[2]
- Voltage Meters[3]
- Inverters & Converters[1]
- Terminals[1]
- Other Passive Components[6]
- Contact Person : Ms. Wan Lisa
- Company Name : Shanghai Shinuo Electric Co., Ltd.
- Tel : 0086-577-61728001
- Fax : 0086-577-61728006
- Address : Zhejiang,Yueqing,Chandong industrial zone
- Country/Region : China
- Zip : 00000
Telemecanique Thermal overload protection relay LR2-D23 JR28-D23
1.Specification
LR2(JR28,VR28) series thermal overload relay are suitable for overload and phase-failure protection of ACmotors with frequency of 50/60Hz, voltage up to 690V, current up to 0.1-150A under 8-hours duty or uninterrupted duty.Functions provided by these relays, are phase-failure protection, ON/OFF indication,temperaturecompensation, and manual/automatic reset.Applicable Standards: National Standard: GB 14048. International Standard: IEC 60947-4-1The relays can be mounted onto contactors or installed as single units.2.Operation condition
(1)The altitude couldn t exceed 2000m.(2)Ambient temperature: -5 ~+55 and the average temperature no more than +35 in 24hours.(3)Atmosphere: Comparative humidity no more than 50% at max +40 , and it may be higher at a lower temperature. The lowest average temperature no more than +20 in the wettest month.The maximum average comparative humidity of this month couldn t exceed 90%, The change of temperature leading to dew on the product must be considered.(4)Class of pollution: Class 3.(5)The slope between installation surface and vertical surface couldn t exceed 5o.(6)Keeping away from explosive, corrosive and electric atomy.(7)Keeping dry.(8)The product should be used and installed at certain place without any shock, vibration etc.
3. Main Technical
Type | Number | Setting range (A) | For contactor |
JR28-25 | 1301 | 0.1~0.16 | CJX2-09~32 |
1302 | 0.16~0.25 | CJX2-09~32 | |
1303 | 0.25~0.4 | CJX2-09~32 | |
1304 | 0.4~0.63 | CJX2-09~32 | |
1305 | 0.63~1 | CJX2-09~32 | |
1306 | 1~1.6 | CJX2-09~32 | |
1307 | 1.6~2.5 | CJX2-09~32 | |
1308 | 2.5~4 | CJX2-09~32 | |
1310 | 4~6 | CJX2-09~32 | |
1312 | 5.5~8 | CJX2-09~32 | |
1314 | 7~10 | CJX2-09~32 | |
1316 | 9~13 | CJX2-09~32 | |
1321 | 12~18 | CJX2-09~32 | |
1322 | 17~25 | CJX2-32 | |
JR28-36 | 2353 | 23~32 | CJX2-09~32 |
2355 | 30~40 | CJX2-09~32 | |
JR28-93 | 3322 | 17~25 | CJX2-09~32 |
3353 | 23~32 | CJX2-09~32 | |
3355 | 30~40 | CJX2-09~32 | |
3357 | 37~50 | CJX2-09~32 | |
3359 | 48~65 | CJX2-09~32 | |
3361 | 55~70 | CJX2-09~32 | |
3363 | 63~80 | CJX2-09~32 | |
3365 | 80~93 | CJX2-95 | |
JR28-150 | 4365 | 80~104 | CJX2-95 |
4367 | 95~120 | CJX2-95~115 | |
4369 | 110~140 | CJX2-115 |
Type | Number | Setting range (A) | For contactor |
JR28-150 | 5369 | 90~150 | CJX2-150 |
JR28-200 | F5357 | 30~50 | CJX2-F115~F185 |
F5363 | 48~80 | CJX2-F115~F185 | |
F5367 | 60~100 | CJX2-F115~F185 | |
F5369 | 90~150 | CJX2-F115~F185 | |
JR28-630 | F5371 | 132~220 | CJX2-F225~F265 |
F7375 | 200~330 | CJX2-F225~F500 | |
F7379 | 300~500 | CJX2-F225~F500 | |
F7381 | 380~630 | CJX2-F400~F630 |
Motion Characteristic: Three-phase Balance Motion Time
No | Times of the setting current | Motion time | Start condition | Ambient temperature | ||
1 | 1.05 | >2h | Cold state | 20±5oC | ||
2 | 1.2 | <2h | Heat state(Following the No.1 test) | |||
3 | 1.5 | <4min | ||||
4 | 7.2 | 10A | 2s< Tp≤10s | ≤63A | Cold state | |
10 | 4s< Tp≤10s | >63A |
Phase-losing Motion Characteristic
No | Times of the setting current | Motion time | Start condition | Ambienttemperature | |
Any two phases | Another phase | ||||
1 | 1.0 | 0.9 | >2h | Cold state | 20±5oC |
2 | 1.15 | 0 | <2h | Heat state(Following the No.1 test) |
4.Packing detail
Model | Carton size(CM) | CTN | WEIGHT |
PCS | (kg) | ||
JR28-25 | 51.5*25.5*30.5 | 100 | 17 |
(LR2-D13) | |||
JR28-36 | 44*39.7*24.3 | 75 | 20 |
(LR2-D23) | |||
JR28-93 | 44*39.7*24.3 | 50 | 23 |
(LR2-D33) | |||
JR28-150 | 44*39.7*24.3 | 50 | 23 |
(LR2-D43) | |||
JR28N-25 | 46.5*27.5*33.5 | 100 | 15 |
(LRD-13) | |||
JR28N-36 | 44*39.7*24.3 | 75 | 20 |
(LRD-23) | |||
JR28N-93 | 44*39.7*24.3 | 50 | 23 |
(LRD-33) | |||
JR28-200 | 47*29*40.5 | 30 | 24 |
(LR9-F53) | |||
JR28-630 | 47*29*40.5 | 18 | 27 |
(LR9-F73) |
5.Overall and Mounting Dimmensions
6.The time-current curves characteristic
7.Accessory
8.Product photo
Telemecanique Thermal overload protection relay LR2-D23 JR28-D23